IGEM/UP/1B Edition 4: what changed

Checked 21 Oct 2026 against IGEM's standard page and FAQ, Gas Safe Register's ISU 133 (Edition 2, 15 April 2026) and Registered Gas Engineer (11 May 2026).

Safety-critical: read the standard, follow your training.

This page is a plain-English summary of public guidance from IGEM and Gas Safe Register. It is not the standard and it is not a substitute for IGEM/UP/1B Edition 4, your ACS training or your own competence. Tightness testing and purging must only be carried out by a Gas Safe registered engineer competent in that work, following the full published standard and the manufacturer's instructions for their gauge. If you smell gas, call the National Gas Emergency Service on 0800 111 999.

Key dates

What changed

  1. Permissible drops depend on installation volume (IV), not meter size alone. The limits are set by fuel gas and IV, and apply only where existing appliances are connected and no smell of gas has been reported (ISU 133; Registered Gas Engineer).
  2. Prove it isn't the pipework. Where there's a perceptible drop within limits, isolate the appliances and retest the pipework only. There must be no perceptible movement on that test. If you can't reasonably isolate an appliance, test with it connected and apply "no perceptible movement" (ISU 133; IGEM FAQ).
  3. Gauge rules for "no perceptible movement": up to 0.25 mbar on a fluid (water) gauge or an electronic gauge, except gauges that read to one decimal place, where it's a maximum of 0.2 mbar (ISU 133).
  4. Purge volume = 1.5 × IV on all installations. You now calculate IV for every purge, even if you didn't need IV for the tightness test (ISU 133; IGEM FAQ). The old assumed PV of 0.01 m³ for pipe up to 28 mm and a meter up to 6 m³/h has gone (Registered Gas Engineer).
  5. Low test pressure. A new note says that if the minimum test pressure for the fuel gas can't be reached, isolate and investigate the low pressure before testing. For natural gas, if 20 mbar can't be achieved, the test can be done at a minimum of 18 mbar, followed by operating pressure checks to IGEM/G/13 (Registered Gas Engineer).
  6. LDF after the test. After a pass, reintroduce appliances and test all disturbed joints with leak detection fluid, plus any installation pipework between an isolation valve and the appliance it serves (ISU 133).

What didn't change

Scope in brief

IGEM says Edition 4 covers installations with a nominal bore up to 35 mm (DN32, R1¼), a meter with badged capacity up to 16 m³/h, an IV up to 0.035 m³, and stated operating pressures (21 mbar for NG and LPG/air, 37 mbar for LPG). It treats natural gas as including blends with up to 20% hydrogen. For IV over 0.035 m³, IGE/UP/1 applies (IGEM).

Does your gauge still work?

The 0.25 mbar / 0.2 mbar rules depend on your gauge's resolution. Our digital manometer guide compares resolutions and built-in tightness tests, with prices checked.

Buying the standard

IGEM listed IGEM/UP/1B Edition 4 at £190.82 (hard copy or 1-year digital licence), or £127.85 for IGEM members, on 21 Oct 2026 (IGEM). Gas Safe registered engineers can read ISU 133 free.

Tightness test reference: the stages step by step →

When did IGEM/UP/1B Edition 4 come in?

IGEM published it in March 2026. It became effective from 1 October 2026, and Edition 3 was withdrawn on 30 September 2026 (IGEM).

What is the main change in IGEM/UP/1B Edition 4?

Gas Safe Register ISU 133 (Edition 2) says permissible pressure drops are now set by the installation volume (IV) rather than meter size alone, and any perceptible movement must be shown not to come from the installation pipework by retesting the pipework only.

Has the purge volume changed?

Yes. ISU 133 says the installation volume must be calculated and purge volume worked out as PV = 1.5 × IV on all installations. Registered Gas Engineer notes that the old assumed PV of 0.01 m³ (for pipe up to 28 mm and a meter up to 6 m³/h) no longer applies.

Can I retest to Edition 3 if a test fails under Edition 4?

No. Registered Gas Engineer says that if a test to the new procedure fails, you must trace and repair the escape or make safe under IGEM/G/11, and recommends recording which version of the test you applied.

Sources (checked 21 Oct 2026)

  1. IGEM: IGEM/UP/1B Edition 4 (standard page and scope)
  2. IGEM: Frequently Asked Questions on IGEM/UP/1B Edition 4
  3. Gas Safe Register: Industry Standard Update 133 (Edition 2, issued 15 Apr 2026), published on Registered Gas Engineer
  4. Registered Gas Engineer: "Updated tightness testing standard: what you need to know", 11 May 2026

GasStack is an independent directory, not a training provider or certification body. This page summarises public sources and is not a substitute for the standards themselves or your training. Spotted something out of date? Tell us.

Get the weekly "What changed" email

One short email a week: price changes, new tools, and one rule or warranty change that matters to gas, heating and plumbing engineers. Free. Unsubscribe any time.

Plus a free starter pack when you confirm: van stock checklist, service reminder templates and a late payment letter (PDF). What's in it

You'll get one email asking you to confirm (double opt-in). Nothing else is sent until you click it. It's free, it's weekly, and you can unsubscribe at any time with the link in every email. Emails are sent by Kit, our newsletter provider.